Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2020, 10:39 AM
  • 01 0798_01 1372_02182020_035601.mp4

Date
02/18/2020
W/O
813501
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00197
PipeID
P21616
Time
2:39 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7457
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_813502_TV01264_FEB2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0798
Downstream MH
01 1372
Dir. of Survey
Downstream
Length Surveyed
339.6 ft.
Total Length
339.6 ft.
Structural Index
4
Structural Quick
4L21
Structural Rating
270
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
4
Overall Quick
Overall Rating
278
Pipe schematic from manhole 01 0798 to 01 1372
MH: 01 0798MH: 01 1372downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 07980 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area3.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"70.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"73.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"121 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6"124 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"171.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"174.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"222.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"225.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"272.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"275.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"318.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"320.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"339 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES - Throughout the reach339 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - Throughout the reach339.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish339.6 ft. AMH - Downstream Manhole, Survey Ends - 01 1372

Observation photos (2)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    121 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (22)

DistanceCodeObservation
121TFD
0AMH01 0798
318.1TF
174.5TFC
272.9TFC
70.5TFC
0MGOCONNECTION AT MH 3 OCLOCK
0MWM
320.6TFC
339.6FM
222.7TF
339DAGSThroughout the reach
73.4TFC
339.6AMH01 1372
28.6TFC
3.1FM
171.6TF
339SSSThroughout the reach
0MWL
124TFC
225.5TFC
275.7TFC

Properties (6)

additional_info
SC398861
custom_field_two
2
customer
LACSD
datetime
2020-02-18T02:39:44-08:00
documentation
PROPIPE
is_lateral_inspection
false