Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2020, 04:20 AM
  • 01 1355_01 0799_02172020_220317.mp4

Date
02/17/2020
W/O
813501
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00197
PipeID
P01503
Time
8:20 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7455
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_813502_TV01264_FEB2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1355
Downstream MH
01 0799
Dir. of Survey
Downstream
Length Surveyed
323.9 ft.
Total Length
323.9 ft.
Structural Index
4
Structural Quick
4K34
Structural Rating
260
O&M Index
3
O&M Quick
4111
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
265
Pipe schematic from manhole 01 1355 to 01 0799
MH: 01 1355MH: 01 0799downstream0 ft. MWL - Water Level, 55 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 13550 ft. MWM - Water Mark, 55 %of cross sectional area4.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20.8 ft. FM - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES24.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish24.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start50.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"68.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"74.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"85 ft. B - Broken, from 11 to 01 o'clock, within 8 inches of joint: YES95.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"116.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"122 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"149 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"163.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"172.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"196.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"208.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"216.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"244.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"255.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"285.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"286.4 ft. RFJ - Roots Fine Joint, from 08 to 02 o'clock, within 8 inches of joint: YES294.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"323.9 ft. AMH - Downstream Manhole, Survey Ends - 01 0799323.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish323.9 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

    20.8 ft. - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    24.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 02 o'clock, within 8 inches of joint: YES

    286.4 ft. - Roots Fine Joint, from 08 to 02 o'clock, within 8 inches of joint: YES

Observations (28)

DistanceCodeObservation
50.7TFC
24.2CM
323.9AMH01 0799
323.9FM
116.2TFC
24.2FM
286.4RFJ
323.9MGOCONNECTION AT MH 3 OCLOCK
0MWL
285.6TFC
74.5TFC
68.8TFC
122TFC
0AMH01 1355
0MWM
20.8FM
216.7TFC
208.2TFC
95.4TFC
294.3TFC
163.9TF
4.6CM
244.1TFC
85B
196.1TFC
172.7TFC
149TFC
255.6TFC

Properties (6)

additional_info
SC398859
custom_field_two
1
customer
LACSD
datetime
2020-02-17T20:20:35-08:00
documentation
PROPIPE
is_lateral_inspection
false