Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2020, 10:09 AM
  • 01 0798A_01 0798_02182020_033854.mp4

Date
02/18/2020
W/O
813501
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00197
PipeID
P01501
Time
2:09 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7457
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_813502_TV01264_FEB2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0798A
Downstream MH
01 0798
Dir. of Survey
Downstream
Length Surveyed
289.5 ft.
Total Length
289.5 ft.
Structural Index
4
Structural Quick
4J3I
Structural Rating
383
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
4
Overall Quick
Overall Rating
389
Pipe schematic from manhole 01 0798A to 01 0798
MH: 01 0798AMH: 01 0798downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 0798A0 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK0 ft. MWM - Water Mark, 60 %of cross sectional area2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start2.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start15 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"38.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"40.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"61.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"79.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"88.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"111.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"126.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"138.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"162.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"170.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"191.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"219 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"242.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"255 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish263.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"289 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - Throughout the reach289 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES - Throughout the reach289.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0798289.5 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK289.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (27)

DistanceCodeObservation
242.7TFC
0MWL
170.9TFC
219TFC
289.5AMH01 0798
15TFC
289SSSThroughout the reach
263.8TFC
79.5TFC
289DAGSThroughout the reach
2.3FM
138.3TFC
289.5MGOCONNECTION AT MH 3 OCLOCK
289.5FM
0AMH01 0798A
255FL
88.1TFC
111.8TFC
191.6TFC
0MGOCONNECTION AT MH 9 OCLOCK
38.5TFC
0MWM
2FL
162.1TFC
61.8TFC
40.9TFC
126.8TFC

Properties (6)

additional_info
SC398861
custom_field_two
1
customer
LACSD
datetime
2020-02-18T02:09:57-08:00
documentation
PROPIPE
is_lateral_inspection
false