Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 21, 2020, 10:21 AM
  • 01 0795_01 0794_02212020_033121.mp4

Date
02/21/2020
W/O
813501
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00197
PipeID
P01497
Time
2:21 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7463
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
LYNWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_813502_TV01264_FEB2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0795
Downstream MH
01 0794
Dir. of Survey
Downstream
Length Surveyed
214.9 ft.
Total Length
214.9 ft.
Structural Index
4
Structural Quick
514H
Structural Rating
305
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
311
Pipe schematic from manhole 01 0795 to 01 0794
MH: 01 0795MH: 01 0794downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 07952 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start2.1 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start46.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"69 ft. B - Broken, from 03 to 06 o'clock, within 8 inches of joint: YES80.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"95.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"119.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"143.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"177.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"185.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"213 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES - Throughout the reach213 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish213 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - Throughout the reach214.9 ft. AMH - Downstream Manhole, Survey Ends - 01 0794214.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish214.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (1)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
2.1FM
177.2TFC
119.7TFC
213DAGSThroughout the reach
46.9TFC
95.5TFC
0MWL
213FL
69B
214.9AMH01 0794
80.5TFC
214.9FM
214.9MGOCONNECTION AT MH 3 O'CLOCK
185.9TFC
213SSSThroughout the reach
0MWM
143.9TFC
2FL
0AMH01 0795

Properties (6)

additional_info
SC398868
custom_field_two
1
customer
LACSD
datetime
2020-02-21T02:21:24-08:00
documentation
PROPIPE
is_lateral_inspection
false