Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 21, 2020, 10:38 AM
  • 04 0080_04 0079 _02212020_040415.mp4

Date
02/21/2020
W/O
813450
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00415
PipeID
P11818
Time
2:38 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7415
Sewer Name
04 SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_813450_TV04009_FEB2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
04 0080
Downstream MH
04 0079
Dir. of Survey
Downstream
Length Surveyed
352.4 ft.
Total Length
352.4 ft.
Structural Index
3
Structural Quick
3L21
Structural Rating
203
O&M Index
2
O&M Quick
322[
O&M Rating
289
Overall Index
2
Overall Quick
Overall Rating
492
Pipe schematic from manhole 04 0080 to 04 0079
MH: 04 0080MH: 04 0079downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MGO - General Observation - ROACHES IN MH0 ft. AMH - Upstream Manhole, Survey Begins - 04 00800 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start4.5 ft. DAZ - Deposits Attached Other, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start - MINERAL15.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start33.7 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"36.7 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"74.2 ft. RFL - Roots Fine Lateral, at 02 o'clock74.2 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"77.3 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"77.3 ft. RFL - Roots Fine Lateral, at 10 o'clock101 ft. ID - Infiltration Dripper, at 02 o'clock, within 8 inches of joint: YES111.2 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES113.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"123.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"155.8 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"155.8 ft. RFL - Roots Fine Lateral, at 11 o'clock174.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"210.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"210.3 ft. RFL - Roots Fine Lateral, at 10 o'clock212.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"253.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"260.6 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"296.4 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"298.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"298.7 ft. RFL - Roots Fine Lateral, at 02 o'clock344.9 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"347 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"350 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - Throughout the reach, from 9 to 3 oclock350.8 ft. DAZ - Deposits Attached Other, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish350.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish350.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish352.4 ft. AMH - Downstream Manhole, Survey Ends - 04 0079

Observation photos (11)

  • General Observation - ROACHES IN MH

    0 ft. - General Observation - ROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Other, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start - MINERAL

    4.5 ft. - Deposits Attached Other, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start - MINERAL

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Lateral, at 02 o'clock

    74.2 ft. - Roots Fine Lateral, at 02 o'clock

  • Roots Fine Lateral, at 10 o'clock

    77.3 ft. - Roots Fine Lateral, at 10 o'clock

  • Infiltration Dripper, at 02 o'clock, within 8 inches of joint: YES

    101 ft. - Infiltration Dripper, at 02 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

    111.2 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

  • Roots Fine Lateral, at 11 o'clock

    155.8 ft. - Roots Fine Lateral, at 11 o'clock

  • Roots Fine Lateral, at 10 o'clock

    210.3 ft. - Roots Fine Lateral, at 10 o'clock

  • Roots Fine Lateral, at 02 o'clock

    298.7 ft. - Roots Fine Lateral, at 02 o'clock

Observations (35)

DistanceCodeObservation
77.3TFA
350.8DAZ
210.3TFA
33.7TFA
350SSSThroughout the reach, from 9 to 3 oclock
260.6TFA
212.3TFA
123.1TFA
113.1TFA
174.2TFA
74.2RFL
101ID
4.5DAZMINERAL
210.3RFL
0MWM
296.4TFA
298.7TFA
253.8TFA
298.7RFL
36.7TFA
350.8CM
0MGOROACHES IN MH
111.2ID
352.4AMH04 0079
77.3RFL
15.3CM
347TFA
155.8TFA
2DAGS
74.2TFA
344.9TFA
0AMH04 0080
0MWL
155.8RFL
350.8DAGS