- Date
- 03/12/2020
- W/O
- 0818533
- Weather
- Light Rain
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00208
- PipeID
- P02158
- Time
- 4:21 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- I0324
- Sewer Name
- 01 HOLMES-WILLOWBROOK TRUNK
- City
- SOUTH GATE
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 10
- Purpose
- Capital Improvement Program Assesment
- Project
- 20200310MDM_HOLMES_WILLOWBROOK_TRUNK
- Material
- NRCP
- Shape
- Circular
- Height
- 18 in.
- Upstream MH
- E 0077
- Downstream MH
- 01 0424
- Dir. of Survey
- Upstream
- Length Surveyed
- 8.8 ft.
- Total Length
- 8.8 ft.
- Structural Index
- 3
- Structural Quick
- 4221
- Structural Rating
- 10
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 10
Pipe schematic from manhole E 0077 to 01 0424 Observation photos (3)

2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

5.5 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG