Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 15, 2020, 10:53 AM
  • A 0685_A 0684 _01152020_031024.mp4

Date
01/15/2020
W/O
803067
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00316
PipeID
P07894
Time
2:53 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7238
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
POMONA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
28
Purpose
Routine Assessment
Project
WO_803067_TV21025_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
39 in.
Upstream MH
A 0685
Downstream MH
A 0684
Dir. of Survey
Downstream
Length Surveyed
910.3 ft.
Total Length
910.3 ft.
Structural Index
3
Structural Quick
5c3c
Structural Rating
1810
O&M Index
2
O&M Quick
2c00
O&M Rating
362
Overall Index
3
Overall Quick
Overall Rating
2172
Pipe schematic from manhole A 0685 to A 0684
MH: A 0685MH: A 0684downstream0 ft. AMH - Upstream Manhole, Survey Begins - A 06850 ft. MGO - General Observation - HEAVY STEAM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT908 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish908 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish909 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish909 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish910.3 ft. AMH - Downstream Manhole, Survey Ends - A 0684

Observations (14)

DistanceCodeObservation
0AMHA 0685
2.1MGOMAG COAT
0MGOHEAVY STEAM
909SSS
2DAGS
2SSS
909SAV
908SRV
2SAV
908DAGS
0MWM
0MWL
2SRV
910.3AMHA 0684

Properties (6)

additional_info
SC398533
custom_field_two
4
customer
LACSD
datetime
2020-01-15T02:53:24-08:00
documentation
PRO PIPE
is_lateral_inspection
false