Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 10, 2020, 09:44 AM
  • 01 0356_01 0355_02102020_020132.mp4

Date
02/10/2020
W/O
808205
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00215
PipeID
P00830
Time
1:44 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7352
Sewer Name
01 NADEAU TRUNK, SECTS 2&1
City
FLORENCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_808205_TV01077_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0356
Downstream MH
01 0355
Dir. of Survey
Downstream
Length Surveyed
210.7 ft.
Total Length
210.7 ft.
Structural Index
3
Structural Quick
4132
Structural Rating
12
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
14
Pipe schematic from manhole 01 0356 to 01 0355
MH: 01 0356MH: 01 0355downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 03560 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start46.3 ft. CM - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES67 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES87 ft. FM - Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES168.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES208.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish210.7 ft. AMH - Downstream Manhole, Survey Ends - 01 0355

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

    46.3 ft. - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    67 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    87 ft. - Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    168.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
168.2CM
0MGOCONNECTION AT MH 9 O'CLOCK
0MWL
210.7AMH01 0355
0AMH01 0356
0MWM
87FM
67CL
208.4DAGS
46.3CM
2DAGS

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-02-10T01:44:26-08:00
documentation
PRO PIPE
is_lateral_inspection
false