Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 10, 2020, 07:15 PM
  • 01 0353_01 0352_02102020_114505.mp4

Date
02/10/2020
W/O
808205
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00215
PipeID
P00827
Time
11:15 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7312
Sewer Name
01 NADEAU TRUNK, SECTS 2&1
City
FLORENCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_808205_TV01077_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0353
Downstream MH
01 0352
Dir. of Survey
Downstream
Length Surveyed
436.1 ft.
Total Length
436.1 ft.
Structural Index
3
Structural Quick
4531
Structural Rating
29
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
31
Pipe schematic from manhole 01 0353 to 01 0352
MH: 01 0353MH: 01 0352downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 03530 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start20.1 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES41.1 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES71.4 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES76.6 ft. FM - Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES86.4 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES158.2 ft. FM - Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES214.5 ft. FM - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES234.2 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES290.8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES436.1 ft. AMH - Downstream Manhole, Survey Ends - 01 0352436.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (9)

  • Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

    20.1 ft. - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    41.1 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    71.4 ft. - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES

    76.6 ft. - Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

    86.4 ft. - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    158.2 ft. - Fracture Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    214.5 ft. - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    234.2 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES

    290.8 ft. - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
20.1FC
436.1AMH01 0352
158.2FM
2DAGS
436.1DAGS
234.2FM
76.6FM
86.4FC
71.4CM
0AMH01 0353
214.5FM
0MWL
0MWM
41.1FM
290.8FC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-02-10T11:15:32-08:00
documentation
PRO PIPE
is_lateral_inspection
false