Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 31, 2020, 07:16 AM
  • 02 1084_02 1083 _01302020_233131.mp4

Date
01/30/2020
W/O
808211
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00282
PipeID
P03658
Time
11:16 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7248
Sewer Name
02 MONTEBELLO DIVERSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_808211_TV02212_JAN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1084
Downstream MH
02 1083
Dir. of Survey
Downstream
Length Surveyed
336.1 ft.
Total Length
336.1 ft.
Structural Index
4
Structural Quick
5L3L
Structural Rating
528
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
528
Pipe schematic from manhole 02 1084 to 02 1083
MH: 02 1084MH: 02 1083downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 10840 ft. MWM - Water Mark, 10 %of cross sectional area2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.7 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start29.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"127 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"275.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"321.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"336 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - Throughout the reach336.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish336.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK336.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1083336.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.7 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0MWL
336.1SAP
29.6TFC
2.1SAP
336.1MGOCONNECTION AT MH 3 O'CLOCK
0AMH02 1084
336.1AMH02 1083
127TF
336.1SRV
321.7TF
0MWM
275.1TF
9.7SRV
336SSSThroughout the reach

Properties (6)

additional_info
SC398547
custom_field_two
2
customer
LACSD
datetime
2020-01-30T23:16:19-08:00
documentation
PROPIPE
is_lateral_inspection
false