Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 7, 2020, 10:33 AM
  • 32 1023_32 1022_02072020_025018.mp4

Date
02/07/2020
W/O
808159
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19471
Time
2:33 AM
Certificate
U-1111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7402
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_808159_TV32025_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 1022
Downstream MH
32 1023
Dir. of Survey
Upstream
Length Surveyed
352.1 ft.
Total Length
352.1 ft.
Structural Index
2
Structural Quick
3J2M
Structural Rating
300
O&M Index
2
O&M Quick
2N00
O&M Rating
152
Overall Index
2
Overall Quick
Overall Rating
452
Pipe schematic from manhole 32 1022 to 32 1023
MH: 32 1022MH: 32 1023upstream0 ft. AMH - Upstream Manhole, Survey Ends - 32 10233.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE4 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish6.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish32 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start - DEPOSITS273.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start335.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN350.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start352.1 ft. MWM - Water Mark, 20 %of cross sectional area352.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start352.1 ft. MWL - Water Level, 15 %of cross sectional area352.1 ft. AMH - Downstream Manhole, Survey Begins - 32 1022

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    79 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start - DEPOSITS

    320.1 ft. - Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start - DEPOSITS

Observations (14)

DistanceCodeObservation
349MGOCONN @ MH 3 O'CLOCK/ACTIVE
346SSS
0MWM
0DAGS
16.5TFOPEN
2SSS
0MWL
79CM
0AMH32 1022
320.1DAZDEPOSITS
348.1DAZ
348.1DAGS
348.1CM
352.1AMH32 1023

Properties (6)

additional_info
SC398791
custom_field_two
3
customer
LACSD
datetime
2020-02-07T02:33:48-08:00
documentation
PRO PIPR
is_lateral_inspection
false