Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 7, 2020, 09:03 AM
  • 32 1022_32 1021_02072020_011726.mp4

Date
02/07/2020
W/O
808159
Weather
Dry
Operator/Surveyor
S.LOPEZ
Sewer ID
Z00841
PipeID
P19470
Time
1:03 AM
Certificate
U-1111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7402
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_808159_TV32025_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 1022
Downstream MH
32 1021
Dir. of Survey
Downstream
Length Surveyed
346.5 ft.
Total Length
346.5 ft.
Structural Index
2
Structural Quick
3L2M
Structural Rating
334
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
2
Overall Quick
Overall Rating
472
Pipe schematic from manhole 32 1022 to 32 1021
MH: 32 1022MH: 32 1021downstream0 ft. AMH - Downstream Manhole, Survey Begins - 32 10220 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start343.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish343.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish344 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish346.5 ft. AMH - Downstream Manhole, Survey Ends - 32 1021

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0AMH32 1022
0DAGS
0MWM
343.8DAGS
344SSS
2CM
2SSS
0MWL
346.5AMH32 1021
343.8CM

Properties (6)

additional_info
SC398791
custom_field_two
3
customer
LACSD
datetime
2020-02-07T01:03:00-08:00
documentation
PRO PIPE
is_lateral_inspection
false