Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 7, 2020, 09:31 AM
  • 32 1020_32 1019 _02072020_015007.mp4

Date
02/07/2020
W/O
808159
Weather
Dry
Operator/Surveyor
S.LOPEZ
Sewer ID
Z00841
PipeID
P19468
Time
1:31 AM
Certificate
U-1111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7402
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_808159_TV32025_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 1020
Downstream MH
32 1019
Dir. of Survey
Downstream
Length Surveyed
389.6 ft.
Total Length
389.6 ft.
Structural Index
3
Structural Quick
3Y2O
Structural Rating
552
O&M Index
2
O&M Quick
2N00
O&M Rating
154
Overall Index
2
Overall Quick
Overall Rating
706
Pipe schematic from manhole 32 1020 to 32 1019
MH: 32 1020MH: 32 1019downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 10200 ft. MWL - Water Level, 20 %of cross sectional area0.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start100.3 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN103.5 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES109.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start385.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish385.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish386 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish386 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish389.6 ft. AMH - Downstream Manhole, Survey Ends - 32 1019

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    103.5 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    109.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0MWM
0.1DAGS
109.6CM
386CM
2SSS
103.5CL
385.9DAGS
0AMH32 1020
389.6AMH32 1019
386SSS
0MWL
385.9CM
100.3TFOPEN
2CM

Properties (6)

additional_info
SC398791
custom_field_two
3
customer
LACSD
datetime
2020-02-07T01:31:00-08:00
documentation
PRO PIPE
is_lateral_inspection
false