Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 10, 2020, 10:07 AM
  • 32 1014_32 1013 _02102020_030849.mp4

Date
02/10/2020
W/O
808159
Weather
Dry
Operator/Surveyor
S.LOPEZ
Sewer ID
Z00841
PipeID
P19462
Time
2:07 AM
Certificate
U-1111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7403
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_808159_TV32025_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 1014
Downstream MH
32 1013
Dir. of Survey
Downstream
Length Surveyed
304.5 ft.
Total Length
304.5 ft.
Structural Index
2
Structural Quick
322K
Structural Rating
126
O&M Index
2
O&M Quick
3122
O&M Rating
10
Overall Index
2
Overall Quick
Overall Rating
136
Pipe schematic from manhole 32 1014 to 32 1013
MH: 32 1014MH: 32 1013downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 10140 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.9 ft. RMJ - Roots Medium Joint, from 02 to 05 o'clock, 10 %, within 8 inches of joint: YESR8.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start41.6 ft. RFJ - Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YESR83.4 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start300 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish301.5 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish301.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish301.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish304.5 ft. AMH - Downstream Manhole, Survey Ends - 32 1013

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    83.4 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

Observations (14)

DistanceCodeObservation
301.5RFJ
0MWL
301.5CM
8.7CM
0AMH32 1014
6.9RMJ
301.5DAGS
2SSS
0DAGS
41.6RFJ
83.4RFJ
0MWM
300SSS
304.5AMH32 1013

Properties (6)

additional_info
SC398792
custom_field_two
2
customer
LACSD
datetime
2020-02-10T02:07:42-08:00
documentation
PRO PIPR
is_lateral_inspection
false