Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 6, 2020, 09:33 AM
  • 32 1041_32 1040A_02062020_014154.mp4

Date
02/06/2020
W/O
808159
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P25702
Time
1:33 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7401
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_808159_TV32025_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 1041
Downstream MH
32 1040A
Dir. of Survey
Downstream
Length Surveyed
185.3 ft.
Total Length
185.3 ft.
Structural Index
2
Structural Quick
3F2F
Structural Rating
177
O&M Index
2
O&M Quick
2F00
O&M Rating
72
Overall Index
2
Overall Quick
Overall Rating
249
Pipe schematic from manhole 32 1041 to 32 1040A
MH: 32 1041MH: 32 1040Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 10410 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start182 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish183.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish183.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish185.3 ft. AMH - Downstream Manhole, Survey Ends - 32 1040A185.3 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
2SSS
0AMH32 1041
182SSS
2DAGS
6CM
183.5CM
185.3AMH32 1040A
0MWM
183.5DAGS
185.3MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MWL

Properties (6)

additional_info
SC398790
custom_field_two
3
customer
LACSD
datetime
2020-02-06T01:33:33-08:00
documentation
PRO PIPE
is_lateral_inspection
false