Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 6, 2020, 08:46 AM
  • 32 1049_32 1048 _02062020_005627.mp4

Date
02/06/2020
W/O
808159
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19496
Time
12:46 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7401
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_808159_TV32025_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 1048
Downstream MH
32 1049
Dir. of Survey
Upstream
Length Surveyed
304 ft.
Total Length
304 ft.
Structural Index
2
Structural Quick
3J2K
Structural Rating
285
O&M Index
2
O&M Quick
2J00
O&M Rating
114
Overall Index
2
Overall Quick
Overall Rating
399
Pipe schematic from manhole 32 1048 to 32 1049
MH: 32 1048MH: 32 1049upstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Ends - 32 10490 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED0.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish275.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start287.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start302 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start304 ft. AMH - Downstream Manhole, Survey Begins - 32 1048304 ft. MWL - Water Level, 40 %of cross sectional area304 ft. MWM - Water Mark, 45 %of cross sectional area

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    28.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    304 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
0AMH32 1048
303.6CM
304MGOCOCKROACHES IN MANHOLE
301SSS
0MWL
2SSS
304AMH32 1049
28.8CM
304MGOCONN @ MH 9 O'CLOCK/CAPPED
0MWM
303.6DAGS
16.9DAGS

Properties (6)

additional_info
SC398790
custom_field_two
3
customer
LACSD
datetime
2020-02-06T00:46:21-08:00
documentation
PRO PIPE
is_lateral_inspection
false