Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 6, 2020, 10:32 AM
  • 32 1043_32 1042 _02062020_030906.mp4

Date
02/06/2020
W/O
808159
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19491
Time
2:32 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7401
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_808159_TV32025_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 1042
Downstream MH
32 1043
Dir. of Survey
Upstream
Length Surveyed
182 ft.
Total Length
182 ft.
Structural Index
3
Structural Quick
3F2F
Structural Rating
175
O&M Index
2
O&M Quick
2F00
O&M Rating
72
Overall Index
2
Overall Quick
Overall Rating
247
Pipe schematic from manhole 32 1042 to 32 1043
MH: 32 1042MH: 32 1043upstream0 ft. AMH - Upstream Manhole, Survey Ends - 32 10431 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish180 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start180 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start182 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start182 ft. MWL - Water Level, 15 %of cross sectional area182 ft. MWM - Water Mark, 20 %of cross sectional area182 ft. AMH - Downstream Manhole, Survey Begins - 32 1042

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
179SSS
0DAGS
182AMH32 1043
2CM
181MGOCONN @ MH 3 O'CLOCK/ACTIVE
2SSS
0MWL
179.9DAGS
0MWM
179CM
0AMH32 1042

Properties (6)

additional_info
SC398790
custom_field_two
3
customer
LACSD
datetime
2020-02-06T02:32:58-08:00
documentation
PRO PIPE
is_lateral_inspection
false