Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 6, 2020, 09:42 AM
  • 32 1040A_32 1040_02062020_014737.mp4

Date
02/06/2020
W/O
808159
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19489
Time
1:42 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7401
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_808159_TV32025_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 1040A
Downstream MH
32 1040
Dir. of Survey
Downstream
Length Surveyed
126 ft.
Total Length
126 ft.
Structural Index
2
Structural Quick
3C2D
Structural Rating
111
O&M Index
2
O&M Quick
2D00
O&M Rating
48
Overall Index
2
Overall Quick
Overall Rating
159
Pipe schematic from manhole 32 1040A to 32 1040
MH: 32 1040AMH: 32 1040downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 1040A0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/DEFECTIVE 75% RAGS/ACTIVE2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start122 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish124 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish124 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish126 ft. AMH - Downstream Manhole, Survey Ends - 32 1040

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
2SSS
2DAGS
0MWM
2CM
124DAGS
126AMH32 1040
0MWL
124CM
122SSS
0AMH32 1040A
0MGOCONN @ MH 9 O'CLOCK/DEFECTIVE 75% RAGS/ACTIVE

Properties (6)

additional_info
SC398790
custom_field_two
3
customer
LACSD
datetime
2020-02-06T01:42:27-08:00
documentation
PRO PIPE
is_lateral_inspection
false