Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 11, 2020, 05:56 AM
  • 32 1037_32 1036_02112020_021944.mp4

Date
02/10/2020
W/O
808159
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19485
Time
9:56 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7404
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_808159_TV32025_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 1037
Downstream MH
32 1036
Dir. of Survey
Downstream
Length Surveyed
393.8 ft.
Total Length
393.8 ft.
Structural Index
3
Structural Quick
4E3N
Structural Rating
501
O&M Index
2
O&M Quick
2O00
O&M Rating
158
Overall Index
3
Overall Quick
Overall Rating
659
Pipe schematic from manhole 32 1037 to 32 1036
MH: 32 1037MH: 32 1036downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 10370 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start17.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start30.1 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 01 to 04 o'clock, , within 8 inches of joint: YES - MINERALS238 ft. FH2 - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start260 ft. CH2 - Crack Longitudinal Hinge, 2, from 08 to 04 o'clock, within 8 inches of joint: YES, Start260 ft. FH2 - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish391 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish391.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish391.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish392 ft. CH2 - Crack Longitudinal Hinge, 2, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish393.8 ft. AMH - Downstream Manhole, Survey Ends - 32 1036

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    17.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Other, 5 %of cross sectional area, from 01 to 04 o'clock,  , within 8 inches of joint: YES - MINERALS

    30.1 ft. - Deposits Attached Other, 5 %of cross sectional area, from 01 to 04 o'clock, , within 8 inches of joint: YES - MINERALS

  • Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    238 ft. - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
17.8CM
0AMH32 1037
393.8AMH32 1036
30.1DAZMINERALS
391.9DAGS
391SSS
4DAGS
391.9CM
0MWM
392CH2
238FH2
2SSS
260CH2
0MWL
260FH2

Properties (6)

additional_info
SC398793
custom_field_two
2
customer
LACSD
datetime
2020-02-10T21:56:15-08:00
documentation
PRO PIPE
is_lateral_inspection