Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 7, 2020, 08:26 AM
  • 32 1033_32 1032_02072020_004001.mp4

Date
02/07/2020
W/O
808159
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19481
Time
12:26 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7402
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_808159_TV32025_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 1033
Downstream MH
32 1032
Dir. of Survey
Downstream
Length Surveyed
348.3 ft.
Total Length
348.3 ft.
Structural Index
3
Structural Quick
524M
Structural Rating
628
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
3
Overall Quick
Overall Rating
766
Pipe schematic from manhole 32 1033 to 32 1032
MH: 32 1033MH: 32 1032downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 32 10332 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12 ft. B - Broken, from 08 to 12 o'clock, within 8 inches of joint: YES12.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start32 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES299 ft. FS - Fracture Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES346 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish346 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish347 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish347 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish348.3 ft. AMH - Downstream Manhole, Survey Ends - 32 1032

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
0MWL
0MWM
12B
2SSS
346FM
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
2DAGS
299FS
348.3AMH32 1032
2FM
32B
347CM
346SSS
12.2CM
347DAGS
0AMH32 1033

Properties (6)

additional_info
SC398791
custom_field_two
2
customer
LACSD
datetime
2020-02-07T00:26:43-08:00
documentation
PRO PIPE
is_lateral_inspection
false