Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 7, 2020, 09:54 AM
  • 08 0008_08 0007_02072020_022854.mp4

Date
02/07/2020
W/O
808144
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00016
PipeID
P00008
Time
1:54 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
k7310
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_808144_TV08115_JAN2020
Sewer Type
Gravity
Material
RCP-CTL
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
08 0008
Downstream MH
08 0007
Dir. of Survey
Downstream
Length Surveyed
305.5 ft.
Total Length
305.5 ft.
Structural Index
4
Structural Quick
4J21
Structural Rating
226
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
230
Pipe schematic from manhole 08 0008 to 08 0007
MH: 08 0008MH: 08 0007downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 00082 ft. MGO - General Observation - MAG COAT THROUGHOUT24.2 ft. MB - Missing Brick, from 09 to 03 o'clock, Start - TILES303 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES303.4 ft. MB - Missing Brick, from 09 to 03 o'clock, Finish303.6 ft. MGO - General Observation - MAG COAT THROUGHOUT END305.5 ft. AMH - Downstream Manhole, Survey Ends - 08 0007

Observation photos (1)

  • Missing Brick, from 09 to 03 o'clock, Start - TILES

    24.2 ft. - Missing Brick, from 09 to 03 o'clock, Start - TILES

Observations (9)

DistanceCodeObservation
303.6MGOMAG COAT THROUGHOUT END
305.5AMH08 0007
2MGOMAG COAT THROUGHOUT
303.4MB
0MWL
24.2MBTILES
0MWM
0AMH08 0008
303SSS

Properties (6)

additional_info
SC378791
custom_field_two
3
customer
LACSD
datetime
2020-02-07T01:54:04-08:00
documentation
PRO PIPE
is_lateral_inspection
false