Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 30, 2020, 11:05 AM
  • A 0581_A 1090 _01302020_032641.mp4

Date
01/30/2020
W/O
803106
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00316
PipeID
P07786
Time
3:05 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7247
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
33
Purpose
Routine Assessment
Project
WO_803106_TV21027_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
72 in.
Width
72 in.
Upstream MH
A 0581
Downstream MH
A 1090
Dir. of Survey
Downstream
Length Surveyed
894.7 ft.
Total Length
894.7 ft.
Structural Index
3
Structural Quick
3c2c
Structural Rating
890
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
890
Pipe schematic from manhole A 0581 to A 1090
MH: A 0581MH: A 1090downstream0 ft. AMH - Upstream Manhole, Survey Begins - A 05810 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.8 ft. MGO - General Observation - MAG COAT3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start890.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish891 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish894.7 ft. AMH - Downstream Manhole, Survey Ends - A 1090

Observations (9)

DistanceCodeObservation
0AMHA 0581
2.8MGOMAG COAT
0MWM
3SSS
890.1SAV
0MWL
891SSS
894.7AMHA 1090
2.2SAV

Properties (6)

additional_info
SC398546
custom_field_two
3
customer
LACSD
datetime
2020-01-30T03:05:30-08:00
documentation
PRO PIPE
is_lateral_inspection
false