Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 21, 2020, 10:35 AM
  • A 0604_A 0603 _01212020_025744.mp4

Date
01/21/2020
W/O
803106
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00316
PipeID
P07809
Time
2:35 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7244
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
37
Purpose
Routine Assessment
Project
WO_803106_TV21027_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Width
51 in.
Upstream MH
A 0604
Downstream MH
A 0603
Dir. of Survey
Downstream
Length Surveyed
1007.6 ft.
Total Length
1007.6 ft.
Structural Index
3
Structural Quick
3g2g
Structural Rating
1000
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
1000
Pipe schematic from manhole A 0604 to A 0603
MH: A 0604MH: A 0603downstream0 ft. AMH - Upstream Manhole, Survey Begins - A 06040 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.8 ft. MGO - General Observation - MAG COAT3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start3.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start1003 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish1004.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1007.6 ft. AMH - Downstream Manhole, Survey Ends - A 0603

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0AMHA 0604
3.9SAP
2.8MGOMAG COAT
3SSS
1007.6AMHA 0603
0MWM
0MWL
1004.7SAP
1003SSS

Properties (6)

additional_info
SC398539
custom_field_two
3
customer
LACSD
datetime
2020-01-21T02:35:22-08:00
documentation
PRO PIPE
is_lateral_inspection
false