Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 23, 2020, 05:35 AM
  • A 0599_A 0598 _01222020_221617.mp4

Date
01/22/2020
W/O
803106
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00316
PipeID
P07804
Time
9:35 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7245
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
37
Purpose
Routine Assessment
Project
WO_803106_TV21027_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
66 in.
Width
66 in.
Upstream MH
A 0599
Downstream MH
A 0598
Dir. of Survey
Downstream
Length Surveyed
899.8 ft.
Total Length
899.9 ft.
Structural Index
3
Structural Quick
3c2c
Structural Rating
893
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
893
Pipe schematic from manhole A 0599 to A 0598
MH: A 0599MH: A 0598downstream0 ft. AMH - Upstream Manhole, Survey Begins - A 05990 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. MGO - General Observation - MAG COAT THROUGHOUT2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start22.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start22.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish707.1 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"895 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish899.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish899.9 ft. AMH - Downstream Manhole, Survey Ends - A 0598

Observations (12)

DistanceCodeObservation
3SSS
895SSS
2MGOMAG COAT THROUGHOUT
899.9AMHA 0598
0AMHA 0599
22.9SAP
0MWM
2SAV
22.9SAV
0MWL
899.7SAP
707.1TFA

Properties (6)

additional_info
SC398543
custom_field_two
3
customer
LACSD
datetime
2020-01-22T21:35:21-08:00
documentation
PRO PIPE
is_lateral_inspection
false