Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 23, 2020, 07:28 AM
  • A 0597_A 1048_01222020_235922.mp4

Date
01/22/2020
W/O
803106
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00316
PipeID
P07802
Time
11:28 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7245
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_803106_TV21027_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
66 in.
Width
66 in.
Upstream MH
A 0597
Downstream MH
A 1048
Dir. of Survey
Downstream
Length Surveyed
593.8 ft.
Total Length
593.8 ft.
Structural Index
3
Structural Quick
3W2V
Structural Rating
588
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
588
Pipe schematic from manhole A 0597 to A 1048
MH: A 0597MH: A 1048downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 05970.1 ft. MWM - Water Mark, 20 %of cross sectional area2.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. MGO - General Observation - MAG COAT THROUGHOUT3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start199.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"590 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish592.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish593.8 ft. AMH - Downstream Manhole, Survey Ends - A 1048

Observations (10)

DistanceCodeObservation
592.7SAP
590SSS
2.2SAP
3SSS
2.2MGOMAG COAT THROUGHOUT
593.8AMHA 1048
0MWL
0.1MWM
0AMHA 0597
199.7TF

Properties (6)

additional_info
SC398543
custom_field_two
3
customer
LACSD
datetime
2020-01-22T23:28:26-08:00
documentation
PRO PIPE
is_lateral_inspection
false