Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 7, 2020, 10:29 AM
  • A 0629_A 0628 _01072020_025144.mp4

Date
01/07/2020
W/O
803106
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00316
PipeID
P07834
Time
2:29 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7233
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
33
Purpose
Routine Assessment
Project
WO_803106_TV21027_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
A 0629
Downstream MH
A 0628
Dir. of Survey
Downstream
Length Surveyed
953.8 ft.
Total Length
953.8 ft.
Structural Index
3
Structural Quick
3e2e
Structural Rating
948
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
948
Pipe schematic from manhole A 0629 to A 0628
MH: A 0629MH: A 0628downstream0 ft. AMH - Upstream Manhole, Survey Begins - A 06290 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start950 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish953.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish953.8 ft. AMH - Downstream Manhole, Survey Ends - A 0628

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
2.1MGOMAG COAT
950SSS
3SSS
953.6SAP
0AMHA 0629
0MWL
0MWM
953.8AMHA 0628
2.1SAP

Properties (6)

additional_info
SC398526
custom_field_two
3
customer
LACSD
datetime
2020-01-07T02:29:59-08:00
documentation
PRO PIPE
is_lateral_inspection
false