Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 9, 2020, 10:01 AM
  • A 0622_A 0621 _01092020_024815.mp4

Date
01/09/2020
W/O
803106
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00316
PipeID
P07827
Time
2:01 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7235
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
33
Purpose
Routine Assessment
Project
WO_803106_TV21027_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
A 0622
Downstream MH
A 0621
Dir. of Survey
Downstream
Length Surveyed
1074.1 ft.
Total Length
1074.1 ft.
Structural Index
3
Structural Quick
3j2j
Structural Rating
1067
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
1067
Pipe schematic from manhole A 0622 to A 0621
MH: A 0622MH: A 0621downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 06220 ft. MWL - Water Level, 10 %of cross sectional area3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start5.2 ft. MGO - General Observation - MAG COAT10.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start1071 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish1074.1 ft. AMH - Downstream Manhole, Survey Ends - A 06211074.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1074.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
1074.1AMHA 0621
5.2MGOMAG COAT
10.1SAV
1074.1SAV
1074.1MGOCONNECTION AT MH 3 O'CLOCK
0MWM
1071SSS
0AMHA 0622
3SSS
0MWL

Properties (6)

additional_info
SC398529
custom_field_two
3
customer
LACSD
datetime
2020-01-09T02:01:44-08:00
documentation
PRO PIPE
is_lateral_inspection
false