Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 9, 2020, 07:56 AM
  • A 0620_A 0619 _01092020_000448.mp4

Date
01/08/2020
W/O
803106
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00316
PipeID
P07825
Time
11:56 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7235
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
33
Purpose
Routine Assessment
Project
WO_803106_TV21027_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
A 0620
Downstream MH
A 0619
Dir. of Survey
Downstream
Length Surveyed
226.6 ft.
Total Length
226.6 ft.
Structural Index
3
Structural Quick
3H2H
Structural Rating
223
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
223
Pipe schematic from manhole A 0620 to A 0619
MH: A 0620MH: A 0619downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 06203 ft. MGO - General Observation - MAG COAT3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start223 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish226.6 ft. AMH - Downstream Manhole, Survey Ends - A 0619226.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWL
0MWM
3MGOMAG COAT
3SAV
0AMHA 0620
226.6AMHA 0619
223SSS
226.6SAV
3SSS

Properties (6)

additional_info
SC398529
custom_field_two
3
customer
LACSD
datetime
2020-01-08T23:56:28-08:00
documentation
PRO PIPE
is_lateral_inspection
false