Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 3, 2020, 08:52 AM
  • A 0647_A 0646A_01032020_011241.mp4

Date
01/03/2020
W/O
803106
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00316
PipeID
P26646
Time
12:52 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7229
Sewer Name
A JOA 1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
34
Purpose
Routine Assessment
Project
WO_803106_TV21027_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
A 0647
Downstream MH
A 0646A
Dir. of Survey
Downstream
Length Surveyed
910.7 ft.
Total Length
910.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole A 0647 to A 0646A
MH: A 0647MH: A 0646Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - A 06470 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT111 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"825.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"910.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish910.7 ft. AMH - Downstream Manhole, Survey Ends - A 0646910.7 ft. MGO - General Observation - NO MH A 0646A

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    111 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (10)

DistanceCodeObservation
0AMHA 0647
0MWM
910.7SAV
910.7AMHA 0646
2.1SAV
825.4TF
111TF
0MWL
2.1MGOMAG COAT
910.7MGONO MH A 0646A

Properties (6)

additional_info
SC398521
custom_field_two
3
customer
LACSD
datetime
2020-01-03T00:52:20-08:00
documentation
PRO PIPE
is_lateral_inspection
false