Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 21, 2020, 07:02 AM
  • A 0656_A 0655 _01202020_231941.mp4

Date
01/20/2020
W/O
803106
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00316
PipeID
P07865
Time
11:02 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7244
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
35
Purpose
Routine Assessment
Project
WO_803106_TV21027_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
A 0656
Downstream MH
A 0655
Dir. of Survey
Downstream
Length Surveyed
833.2 ft.
Total Length
833.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole A 0656 to A 0655
MH: A 0656MH: A 0655downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 06562.8 ft. MGO - General Observation - MAG COAT11.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start234.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"826.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish833.2 ft. AMH - Downstream Manhole, Survey Ends - A 0655

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
826.7SAV
234.7TF
11.5SAV
0MWM
0MWL
2.8MGOMAG COAT
833.2AMHA 0655
0AMHA 0656

Properties (6)

additional_info
SC398539
custom_field_two
3
customer
LACSD
datetime
2020-01-20T23:02:15-08:00
documentation
PRO PIPE
is_lateral_inspection
false