Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 6, 2020, 10:38 AM
  • A 0639_A 0638 _01062020_025814.mp4

Date
01/06/2020
W/O
803106
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00316
PipeID
P07844
Time
2:38 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7232
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
34
Purpose
Routine Assessment
Project
WO_803106_TV21027_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
45 in.
Width
45 in.
Upstream MH
A 0639
Downstream MH
A 0638
Dir. of Survey
Downstream
Length Surveyed
977.6 ft.
Total Length
977.6 ft.
Structural Index
3
Structural Quick
3f2f
Structural Rating
973
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
973
Pipe schematic from manhole A 0639 to A 0638
MH: A 0639MH: A 0638downstream0 ft. AMH - Upstream Manhole, Survey Begins - A 06390 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2.6 ft. MGO - General Observation - MAG COAT2.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start234.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"626.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"695.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"958.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"968.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO, Start968.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish973 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish977.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish977.6 ft. AMH - Downstream Manhole, Survey Ends - A 0638

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    968.5 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

Observations (15)

DistanceCodeObservation
968.5SAP
958.6TF
695.2TF
0AMHA 0639
0MWL
973SSS
968.5SAV
234.1TF
0MWM
2.6MGOMAG COAT
977.6AMHA 0638
3SSS
626.7TF
977.5SAP
2.6SAV

Properties (6)

additional_info
SC398525
custom_field_two
3
customer
LACSD
datetime
2020-01-06T02:38:31-08:00
documentation
PRO PIPE
is_lateral_inspection
false