Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 27, 2020, 08:45 PM
  • A 0664_A 0663 _01272020_130118.mp4

Date
01/27/2020
W/O
803106
Weather
Dry
Operator/Surveyor
N. ZAHREDDINE
Sewer ID
Z00316
PipeID
P07873
Time
12:45 PM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7306
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
35
Purpose
Routine Assessment
Project
WO_803106_TV21027_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
39 in.
Upstream MH
A 0664
Downstream MH
A 0663
Dir. of Survey
Downstream
Length Surveyed
777.6 ft.
Total Length
777.6 ft.
Structural Index
3
Structural Quick
3^2^
Structural Rating
770
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
770
Pipe schematic from manhole A 0664 to A 0663
MH: A 0664MH: A 0663downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 06640 ft. MWL - Water Level, 25 %of cross sectional area2 ft. MGO - General Observation - MAG COAT THROUGHOUT3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start201 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"449.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 8"771 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish771.9 ft. MGO - General Observation - MAG COAT THROUGHOUT END774 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish777.6 ft. AMH - Downstream Manhole, Survey Ends - A 0663

Observations (12)

DistanceCodeObservation
201TF
2MGOMAG COAT THROUGHOUT
771SSS
3SSS
0MWM
774SAV
771.9MGOMAG COAT THROUGHOUT END
3SAV
449.7TFA
777.6AMHA 0663
0AMHA 0664
0MWL

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-01-27T12:45:00-08:00
documentation
PRO PIPE
is_lateral_inspection
false