Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 11, 2020, 09:24 AM
  • J 0050_J 0048 _02112020_013954.mp4

Date
02/11/2020
W/O
808664
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00062
PipeID
P11627
Time
1:24 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7451
Sewer Name
J JOINT OUTFALL J - UNIT 2C
City
LOMITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Routine Assessment
Project
RFIR_WO_808664_TV05287_JAN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
J 0050
Downstream MH
J 0048
Dir. of Survey
Downstream
Length Surveyed
566.7 ft.
Total Length
566.7 ft.
Structural Index
3
Structural Quick
513V
Structural Rating
570
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
570
Pipe schematic from manhole J 0050 to J 0048
MH: J 0050MH: J 0048downstream0 ft. AMH - Upstream Manhole, Survey Begins - J 00500 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start499.7 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO564 ft. MGO - General Observation - MAG COAT THROUGHOUT564.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish564.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish566.7 ft. AMH - Downstream Manhole, Survey Ends - J 0048

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

    499.7 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

Observations (10)

DistanceCodeObservation
499.7SRV
564.7SAP
564.7SSS
564MGOMAG COAT THROUGHOUT
566.7AMHJ 0048
2.1SSS
0AMHJ 0050
0MWL
2.1SAP
0MWM

Properties (6)

additional_info
SC398855
custom_field_two
2
customer
LACSD
datetime
2020-02-11T01:24:06-08:00
documentation
PROPIPE
is_lateral_inspection
false