Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2016, 08:14 AM
  • 02 0005_02 0132_1182016_012111.mp4

Date
11/08/2016
W/O
0596969
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00234
PipeID
P03030
Time
12:14 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0337
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Capital Improvement Program Assesment
Project
20161103MDM_ARTESIA_EXTENSION_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
02 0132
Downstream MH
02 0005
Dir. of Survey
Upstream
Length Surveyed
6.8 ft.
Total Length
6.9 ft.
Structural Index
5
Structural Quick
5241
Structural Rating
14
O&M Index
4
O&M Quick
5131
O&M Rating
8
Overall Index
4
Overall Quick
Overall Rating
22
Pipe schematic from manhole 02 0132 to 02 0005
MH: 02 0132MH: 02 0005upstream0 ft. MSA - Survey Abandoned - UPLEG DOWNSTREAM SIPHON NORTH0.4 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG0.4 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: NO0.9 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR4.9 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG4.9 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR4.9 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM6.9 ft. AMH - Downstream Manhole, Survey Begins - 1:20AM6.9 ft. MWM - Water Mark, 80 %of cross sectional area6.9 ft. MWL - Water Level, 60 %of cross sectional area

Observation photos (5)

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    2 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    2 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Deposits Attached Grease, 15 %of cross sectional area, from 11 to 01 o'clock,  , within 8 inches of joint: NO

    6.5 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: NO

  • Survey Abandoned - UPLEG DOWNSTREAM SIPHON NORTH

    6.9 ft. - Survey Abandoned - UPLEG DOWNSTREAM SIPHON NORTH

Observations (10)

DistanceCodeObservation
0AMH1:20AM
6.5SAMSEVERE AGG
6.9MSAUPLEG DOWNSTREAM SIPHON NORTH
6.5DAGS
6SRVCIRCUM REBAR
0MWM
2SAMSEVERE AGG
2SRVCIRCUM REBAR
2SRVCIRCUM
0MWL

Properties (7)

additional_info
UPLEG DOWNSTREAM SIPHON NORTH
custom_field_three
MISSING SEVERE AGG - CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2016-11-08T00:14:31-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER V111
is_lateral_inspection
false