Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2016, 08:14 AM
  • 02 0005_02 0132_1182016_013629.mp4

Date
11/08/2016
W/O
0596969
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00234
PipeID
P18010
Time
12:14 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0337
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Capital Improvement Program Assesment
Project
20161103MDM_ARTESIA_EXTENSION_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
02 0132
Downstream MH
02 0005
Dir. of Survey
Upstream
Length Surveyed
10.5 ft.
Total Length
10.5 ft.
Structural Index
4
Structural Quick
5141
Structural Rating
11
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
15
Pipe schematic from manhole 02 0132 to 02 0005
MH: 02 0132MH: 02 0005upstream0 ft. MSA - Survey Abandoned - UPLEG DOWNSTREAM SIPHON SOUTH0.5 ft. SAM - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG0.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish2.5 ft. SMW - Surface Missing Wall, at 12 o'clock, within 8 inches of joint: NO - 10" X10"8.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SWOLLEN FLAKING LAITANCE COAT8.5 ft. SAM - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG10.5 ft. MWL - Water Level, 40 %of cross sectional area - NO FLOW STOPLOG IN PLACE10.5 ft. MWM - Water Mark, 50 %of cross sectional area - STANDING WATER AND SLUDGE10.5 ft. AMH - Downstream Manhole, Survey Begins - 1:35AM

Observation photos (5)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SWOLLEN FLAKING LAITANCE COAT

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SWOLLEN FLAKING LAITANCE COAT

  • Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Missing Wall, at 12 o'clock, within 8 inches of joint: NO - 10" X10"

    8 ft. - Surface Missing Wall, at 12 o'clock, within 8 inches of joint: NO - 10" X10"

  • Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG

    10 ft. - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG

  • Survey Abandoned - UPLEG DOWNSTREAM SIPHON SOUTH

    10.5 ft. - Survey Abandoned - UPLEG DOWNSTREAM SIPHON SOUTH

Observations (9)

DistanceCodeObservation
0MWLNO FLOW STOPLOG IN PLACE
0MWMSTANDING WATER AND SLUDGE
2SSSSWOLLEN FLAKING LAITANCE COAT
2SAMSEVERE AGG
10SAMSEVERE AGG
0AMH1:35AM
8SMW10" X10"
10.5MSAUPLEG DOWNSTREAM SIPHON SOUTH
10SSS

Properties (7)

additional_info
UPLEG DOWNSTREAM SIPHON SOUTH
custom_field_three
MISSING PIPE SOIL VISIBLE
custom_field_two
1
customer
LACSD
datetime
2016-11-08T00:14:19-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER V111
is_lateral_inspection
false