Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 9, 2020, 08:38 PM
  • 29 0268A_29 0268 _01092020_131507.mp4

Date
01/09/2020
W/O
808558
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00550
PipeID
P24174
Time
12:38 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6844
Sewer Name
29 WEST HILL STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_808558_TV29063_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0268
Downstream MH
29 0268A
Dir. of Survey
Upstream
Length Surveyed
225.7 ft.
Total Length
225.7 ft.
Structural Index
2
Structural Quick
3222
Structural Rating
11
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
11
Pipe schematic from manhole 29 0268 to 29 0268A
MH: 29 0268MH: 29 0268Aupstream0 ft. ACOM - Cleanout Mainline, Survey Ends - 29 0268A3.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"10.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"15.3 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES43.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"52 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"66.6 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"84.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"102.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"144 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"146.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"155.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"190.1 ft. JOM - Joint Offset Medium217.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES221.6 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES221.6 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES225.7 ft. MWL - Water Level, 5 %of cross sectional area225.7 ft. AMH - Downstream Manhole, Survey Begins - 29 0268225.7 ft. MWM - Water Mark, 10 %of cross sectional area

Observation photos (5)

  • Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    4.1 ft. - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES

    4.1 ft. - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    8.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Joint Offset Medium

    35.6 ft. - Joint Offset Medium

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    210.4 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
173.7TFC
8.5CL
81.7TFC
123.1TFC
225.7ACOM29 0268A
182TF
4.1CM
4.1FS
79.1TFC
0MWL
214.8TF
140.9TFC
210.4CL
0AMH29 0268
70.5TF
159.1TBA
0MWM
222.6TFC
35.6JOM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-01-09T12:38:24-08:00
documentation
PRO PIPE
is_lateral_inspection
false