Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 9, 2020, 09:24 PM
  • 29 0268_29 0267 _01092020_134650.mp4

Date
01/09/2020
W/O
808558
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00550
PipeID
P24173
Time
1:24 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6844
Sewer Name
29 WEST HILL STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_808558_TV29063_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0268
Downstream MH
29 0267
Dir. of Survey
Downstream
Length Surveyed
324.5 ft.
Total Length
324.5 ft.
Structural Index
3
Structural Quick
3D23
Structural Rating
84
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
84
Pipe schematic from manhole 29 0268 to 29 0267
MH: 29 0268MH: 29 0267downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 02680 ft. MWM - Water Mark, 15 %of cross sectional area42.7 ft. CM - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES77.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"79.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"81.2 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES90.1 ft. CM - Crack Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES127.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"128.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES130.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"178 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"180.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"183.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"196.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES202.6 ft. CM - Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES, Start234.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"281.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"284.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"321.4 ft. CM - Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES, Finish324.5 ft. AMH - Downstream Manhole, Survey Ends - 29 0267

Observation photos (6)

  • Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

    42.7 ft. - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    81.2 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES

    90.1 ft. - Crack Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    128.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    196.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES, Start

    202.6 ft. - Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
127.7TF
321.4CM
0MWL
202.6CM
196.7CL
0AMH29 0268
178TF
281.8TF
90.1CM
77.2TF
180.6TF
42.7CM
284.3TF
130.4TFC
81.2CL
234.3TF
324.5AMH29 0267
79.6TF
0MWM
183.2TF
128.8CL

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-01-09T13:24:57-08:00
documentation
PRO PIPE
is_lateral_inspection
false