Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 9, 2020, 09:47 PM
  • 29 0267_29 0266 _01092020_141647.mp4

Date
01/09/2020
W/O
808558
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00550
PipeID
P24172
Time
1:47 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6844
Sewer Name
29 WEST HILL STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_808558_TV29063_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0267
Downstream MH
29 0266
Dir. of Survey
Downstream
Length Surveyed
331.4 ft.
Total Length
331.4 ft.
Structural Index
3
Structural Quick
5142
Structural Rating
182
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
182
Pipe schematic from manhole 29 0267 to 29 0266
MH: 29 0267MH: 29 0266downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 02674.1 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES4.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"6.9 ft. CL - Crack Longitudinal, at 05 o'clock, within 8 inches of joint: YES7 ft. B - Broken, from 05 to 07 o'clock, within 8 inches of joint: YES7.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"10.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"47.9 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES57.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start58.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"63.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"102 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"119.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"164.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"213.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"215.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"218.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"255.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"259 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"309.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"323.8 ft. B - Broken, from 12 to 02 o'clock, within 8 inches of joint: YES324.1 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: NO326.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish331.4 ft. AMH - Downstream Manhole, Survey Ends - 29 0266

Observation photos (7)

  • Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    4.1 ft. - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 05 o'clock, within 8 inches of joint: YES

    6.9 ft. - Crack Longitudinal, at 05 o'clock, within 8 inches of joint: YES

  • Broken, from 05 to 07 o'clock, within 8 inches of joint: YES

    7 ft. - Broken, from 05 to 07 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    47.9 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    57.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 12 to 02 o'clock, within 8 inches of joint: YES

    323.8 ft. - Broken, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: NO

    324.1 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: NO

Observations (26)

DistanceCodeObservation
10.6TF
0MWM
218.5TFC
331.4AMH29 0266
324.1FM
326.1CM
164.5TF
215.4TF
0MWL
213.9TB
7B
0AMH29 0267
102TF
7.8TFC
47.9CL
119.7TF
63.7TF
309.5TF
4.8TF
6.9CL
57.1CM
58.2TF
259TF
323.8B
4.1CM
255.9TF

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2020-01-09T13:47:39-08:00
documentation
PRO PIPE
is_lateral_inspection
false