Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 11, 2020, 10:14 AM
  • 02 2093_02 2092_02112020_024305.mp4

Date
02/11/2020
W/O
808201
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00283
PipeID
P04194
Time
2:14 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7353
Sewer Name
02 MONTEBELLO INTERCEPTOR TRUNK, SECTS 1&2
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_808201_TV02213_JAN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
02 2093
Downstream MH
02 2092
Dir. of Survey
Downstream
Length Surveyed
486.5 ft.
Total Length
486.5 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
14
Pipe schematic from manhole 02 2093 to 02 2092
MH: 02 2093MH: 02 2092downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 20932 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start244.8 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start485.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish485.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish485.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish486.5 ft. AMH - Downstream Manhole, Survey Ends - 02 2092

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    244.8 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0MWL
486.5AMH02 2092
485.3SSS
244.8SRV
0MWM
485.3SAP
0AMH02 2093
2SSS
485.3SRV
2SAP

Properties (7)

custom_field_three
REINFORCEMENT VISIBLE
custom_field_two
2
customer
LACSD
datetime
2020-02-11T02:14:40-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
30160