Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 11, 2020, 09:12 AM
  • 02 1845_02 1844_02112020_013005.mp4

Date
02/11/2020
W/O
808201
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00283
PipeID
P04190
Time
1:12 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7353
Sewer Name
02 MONTEBELLO INTERCEPTOR TRUNK, SECTS 1&2
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_808201_TV02213_JAN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
02 1845
Downstream MH
02 1844
Dir. of Survey
Downstream
Length Surveyed
445.9 ft.
Total Length
445.9 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
14
Pipe schematic from manhole 02 1845 to 02 1844
MH: 02 1845MH: 02 1844downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 18450 ft. MWL - Water Level, 30 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14.6 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start443.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish443.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish443.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish445.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1844

Observation photos (1)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    14.6 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0MWM
443.4SSS
445.9AMH02 1844
0AMH02 1845
2SSS
14.6SRV
443.4SAP
443.3SRV
0MWL
2SAP

Properties (6)

custom_field_three
REINFORCEMENT VISIBLE
custom_field_two
2
customer
LACSD
datetime
2020-02-11T01:12:20-08:00
documentation
PRO PIPE
is_lateral_inspection
false