- Date
- 02/27/2020
- W/O
- 0813455
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00315
- PipeID
- P07745
- Time
- 12:17 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1370
- Sewer Name
- A JOA-1A DISTRICT 5 INTERCEPTOR
- City
- GARDENA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 20
- Purpose
- Capital Improvement Program Assesment
- Project
- 20200220MDM_JOA_1A_DISTRICT_5_INTERCEPTOR
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 54 in.
- Upstream MH
- A 0537
- Downstream MH
- A 0538
- Dir. of Survey
- Upstream
- Length Surveyed
- 24.8 ft.
- Total Length
- 24.8 ft.
- Structural Index
- 2
- Structural Quick
- 3122
- Structural Rating
- 7
- O&M Index
- 2
- O&M Quick
- 2100
- O&M Rating
- 2
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 9
Pipe schematic from manhole A 0537 to A 0538 Observation photos (5)

10 ft. - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - FALLEN SPALLING CONCRETE

10 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

10 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

15.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING LATANCE COAT

15.7 ft. - General Observation - 39" RCP