Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 20, 2020, 09:46 AM
  • A 0514_A 0513_2202020_015428.mp4

Date
02/20/2020
W/O
0813459
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00315
PipeID
P07750
Time
1:46 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1364
Sewer Name
A JOA-1A DISTRICT 5 INTERCEPTOR
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Capital Improvement Program Assesment
Project
20200220MDM_JOA_1A_DISTRICT_5_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Upstream MH
A 0514
Downstream MH
A 0513
Dir. of Survey
Downstream
Length Surveyed
816.8 ft.
Total Length
816.8 ft.
Structural Index
5
Structural Quick
5641
Structural Rating
34
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
34
Pipe schematic from manhole A 0514 to A 0513
MH: A 0514MH: A 0513downstream0 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR & MISSING0 ft. AMH - Upstream Manhole, Survey Begins - 1:50AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - MAG COAT 90% START2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG7.5 ft. SRC - Surface Reinforcement Corroded, from 08 to 11 o'clock, within 8 inches of joint: NO - MISSING REBAR34.8 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR279 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR& MISSING508 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR737.6 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES - CIRCUM REBAR UNDER MAG COAT816.2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR & MISSING816.2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG816.2 ft. MGO - General Observation - MAG COAT 90% FINISH816.8 ft. AMH - Downstream Manhole, Survey Ends - 2:35AM

Observation photos (8)

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR & MISSING

    0 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR & MISSING

  • General Observation - MAG COAT 90% START

    0 ft. - General Observation - MAG COAT 90% START

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 08 to 11 o'clock, within 8 inches of joint: NO - MISSING REBAR

    7.5 ft. - Surface Reinforcement Corroded, from 08 to 11 o'clock, within 8 inches of joint: NO - MISSING REBAR

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR

    34.8 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR& MISSING

    279 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR& MISSING

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR

    508 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES - CIRCUM REBAR UNDER MAG COAT

    737.6 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES - CIRCUM REBAR UNDER MAG COAT

Observations (15)

DistanceCodeObservation
0SRCLONG & CIRCUM REBAR & MISSING
2SAMSEVERE AGG
816.2SRCLONG & CIRCUM REBAR & MISSING
0AMH1:50AM
0MWM
0MWL
816.2SAMSEVERE AGG
816.2MGOMAG COAT 90% FINISH
0MGOMAG COAT 90% START
7.5SRCMISSING REBAR
737.6SRCCIRCUM REBAR UNDER MAG COAT
508SRCCORRODED MISSING REBAR
279SRCLONG CIRCUM REBAR& MISSING
816.8AMH2:35AM
34.8SRCCORRODED MISSING REBAR

Properties (6)

custom_field_three
LONG & CIRCUM REBAR CORRODED & MISSING-90% MAG COA
custom_field_two
2
customer
LACSD
datetime
2020-02-20T01:46:23-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false