Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 3, 2020, 09:55 AM
  • 15 0747_15 0746_332020_020304.mp4

Date
03/03/2020
W/O
0813511
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12957
Time
1:55 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1373
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20200226MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0747
Downstream MH
15 0746
Dir. of Survey
Downstream
Length Surveyed
346.8 ft.
Total Length
346.8 ft.
Structural Index
2
Structural Quick
4131
Structural Rating
21
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
25
Pipe schematic from manhole 15 0747 to 15 0746
MH: 15 0747MH: 15 0746downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:55AM0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CONCRETE PEELING OUTER LAYER2 ft. MGO - General Observation - 20% MAG COAT START3.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - THICKER PEELING CONCRETE BEGINING21.4 ft. SSS - Surface Spalling, from 09 to 12 o'clock, within 8 inches of joint: NO - BEGINING PEELING CONCRETE SEVERE AGG ATTACHED33.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active73.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open86 ft. SSS - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - BEGINING PELING CONCRETE SEVERE AGG ATTACHED97.8 ft. MGO - General Observation - 60% MAG COAT START103.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open118.7 ft. SSS - Surface Spalling, from 09 to 11 o'clock, within 8 inches of joint: YES - PEELING CONCRETE SEVERE AGG ATTACHED118.7 ft. SAM - Surface Aggregate Missing, from 08 to 11 o'clock, within 8 inches of joint: YES - SEVERE AGG135.4 ft. MGO - General Observation - 10% MAG COAT START167.5 ft. SSS - Surface Spalling, from 09 to 11 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED178 ft. MGO - General Observation - 60% MAG COAT START178 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open204.9 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open225.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open283.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open286.2 ft. SSS - Surface Spalling, from 09 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED346.3 ft. MGO - General Observation - 60% MAG COAT FINISH346.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE OUTER LAYER346.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG346.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BEGINING PEELING CONCRETRE SEVERE AGG ATTACHED346.8 ft. AMH - Downstream Manhole, Survey Ends - 1:30AM

Observation photos (10)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CONCRETE PEELING OUTER LAYER

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CONCRETE PEELING OUTER LAYER

  • General Observation - 20% MAG COAT START

    2 ft. - General Observation - 20% MAG COAT START

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - THICKER PEELING CONCRETE BEGINING

    3.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - THICKER PEELING CONCRETE BEGINING

  • Surface Spalling, from 09 to 12 o'clock, within 8 inches of joint: NO - BEGINING PEELING CONCRETE SEVERE AGG ATTACHED

    21.4 ft. - Surface Spalling, from 09 to 12 o'clock, within 8 inches of joint: NO - BEGINING PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - BEGINING PELING CONCRETE SEVERE AGG ATTACHED

    86 ft. - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - BEGINING PELING CONCRETE SEVERE AGG ATTACHED

  • Surface Spalling, from 09 to 11 o'clock, within 8 inches of joint: YES - PEELING CONCRETE SEVERE AGG ATTACHED

    118.7 ft. - Surface Spalling, from 09 to 11 o'clock, within 8 inches of joint: YES - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Aggregate Missing, from 08 to 11 o'clock, within 8 inches of joint: YES - SEVERE AGG

    118.7 ft. - Surface Aggregate Missing, from 08 to 11 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Spalling, from 09 to 11 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    167.5 ft. - Surface Spalling, from 09 to 11 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Spalling, from 09 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    286.2 ft. - Surface Spalling, from 09 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

Observations (29)

DistanceCodeObservation
86SSSBEGINING PELING CONCRETE SEVERE AGG ATTACHED
3.2SSSTHICKER PEELING CONCRETE BEGINING
21.4SSSBEGINING PEELING CONCRETE SEVERE AGG ATTACHED
135.4MGO10% MAG COAT START
0MWL
2SAPSEVERE AGG
286.2SSSPEELING CONCRETE SEVERE AGG ATTACHED
0AMH1:55AM
2SSSCONCRETE PEELING OUTER LAYER
33.7TFActive
283.4TFOpen
97.8MGO60% MAG COAT START
103.8TFOpen
346.7SSSPEELING CONCRETE OUTER LAYER
178MGO60% MAG COAT START
178TFOpen
346.7SAPSEVERE AGG
346.3MGO60% MAG COAT FINISH
2MGO20% MAG COAT START
346.8AMH1:30AM
73.6TFOpen
118.7SSSPEELING CONCRETE SEVERE AGG ATTACHED
346.7SSSBEGINING PEELING CONCRETRE SEVERE AGG ATTACHED
0MWM
118.7SAMSEVERE AGG
0MGOConn. @ Mh, 3 O' Clock. Active
167.5SSSPEELING CONCRETE SEVERE AGG ATTACHED
225.8TFOpen
204.9TFOpen

Properties (6)

custom_field_three
BEGINING OF PEELING CONCRETE SEVERE AGG ATTACHED
custom_field_two
2
customer
LACSD
datetime
2020-03-03T01:55:28-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false