- Date
- 03/02/2020
- W/O
- 0813511
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00593
- PipeID
- P12950
- Time
- 3:47 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1372
- Sewer Name
- 15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
- City
- ARCADIA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 04
- Purpose
- Capital Improvement Program Assesment
- Project
- 20200226MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
- Material
- NRCP
- Shape
- Circular
- Height
- 15 in.
- Upstream MH
- 15 0750
- Downstream MH
- 15 0749
- Dir. of Survey
- Downstream
- Length Surveyed
- 315 ft.
- Total Length
- 315 ft.
- Structural Index
- 3
- Structural Quick
- 4123
- Structural Rating
- 10
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 10
Pipe schematic from manhole 15 0750 to 15 0749 Observation photos (6)

2 ft. - General Observation - 80% MAG COAT START

2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

9.3 ft. - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: NO - DEEP PEELING CONCRETE

36.2 ft. - General Observation - 90% MAG COAT

127.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED