Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 2, 2020, 08:38 AM
  • 15 0766_15 0755_322020_005656.mp4

Date
03/02/2020
W/O
0813511
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12956
Time
12:38 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1372
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20200226MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0756
Downstream MH
15 0755
Dir. of Survey
Downstream
Length Surveyed
330.2 ft.
Total Length
330.2 ft.
Structural Index
3
Structural Quick
4223
Structural Rating
14
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
18
Pipe schematic from manhole 15 0756 to 15 0755
MH: 15 0756MH: 15 0755downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 12:45AM2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SE4VERE AGG2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED8.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped12.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING BCONCRETE SEVERE AGG ATTACHED48.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped62.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED63.5 ft. MGP - General Photograph - PEELING CONCRETE SEVERE AGG ATTACEC66.7 ft. MGO - General Observation - OLD MAG COAT 10%71.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open79.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active152.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open154.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped161.9 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - DEEP PEELING CONCRETE203.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open285.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open330.2 ft. AMH - Downstream Manhole, Survey Ends - 1:15AM330.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG330.2 ft. MGO - General Observation - MAG COAT 10% FINISH330.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE SEVERE AGG ATTACHED

Observation photos (7)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SE4VERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SE4VERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING BCONCRETE SEVERE AGG ATTACHED

    12.5 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING BCONCRETE SEVERE AGG ATTACHED

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    62.5 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

  • General Photograph - PEELING CONCRETE SEVERE AGG ATTACEC

    63.5 ft. - General Photograph - PEELING CONCRETE SEVERE AGG ATTACEC

  • General Observation - OLD MAG COAT 10%

    66.7 ft. - General Observation - OLD MAG COAT 10%

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - DEEP PEELING CONCRETE

    161.9 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - DEEP PEELING CONCRETE

Observations (23)

DistanceCodeObservation
203.6TFOpen
0MWM
285.7TFOpen
161.9SAMDEEP PEELING CONCRETE
330.2AMH1:15AM
12.5SSSPEELING BCONCRETE SEVERE AGG ATTACHED
79.2TFAActive
330.2SAMSEVERE AGG
71.2TFOpen
0MWL
62.5SSSPEELING CONCRETE SEVERE AGG ATTACHED
2SAMSE4VERE AGG
154.9TFCCapped
48.5TFCCapped
330.2MGOMAG COAT 10% FINISH
330.2SSSPEELING CONCRETE SEVERE AGG ATTACHED
0MGOConn. @ Mh, 9 O' Clock. Active
0AMH12:45AM
2SSSPEELING CONCRETE SEVERE AGG ATTACHED
66.7MGOOLD MAG COAT 10%
152.2TFOpen
8.8TFCCapped
63.5MGPPEELING CONCRETE SEVERE AGG ATTACEC

Properties (6)

custom_field_three
DEEP PEELING CONCRETE SEVERE AGG ATTACHED
custom_field_two
1
customer
LACSD
datetime
2020-03-02T00:38:27-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false