Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 26, 2020, 08:42 AM
  • 15 0765_15 0764_2262020_005224.mp4

Date
02/26/2020
W/O
0813511
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12966
Time
12:42 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1369
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20200226MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0765
Downstream MH
15 0764
Dir. of Survey
Downstream
Length Surveyed
209.6 ft.
Total Length
209.6 ft.
Structural Index
3
Structural Quick
4223
Structural Rating
14
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
14
Pipe schematic from manhole 15 0765 to 15 0764
MH: 15 0765MH: 15 0764downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 12:50AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - FALKING CONCRETE2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG16.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING FLAKING CONCRETE SEVERE AGG ATTACHED16.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - FLAKING CONCRETE31.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED38 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG55.9 ft. MGO - General Observation - 30% MAG COAT START67 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open87.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped90.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped117.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open120.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped148.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open209 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - PEELING FLAKING CONCRETE SEVERE AGG ATTACHED209 ft. MGO - General Observation - MAG COAT 30% FINISH209 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE209 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active209.6 ft. AMH - Downstream Manhole, Survey Ends - 1:20AM

Observation photos (6)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - FALKING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - FALKING CONCRETE

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING FLAKING CONCRETE SEVERE AGG ATTACHED

    16.6 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING FLAKING CONCRETE SEVERE AGG ATTACHED

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    31.5 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    38 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Observation - 30% MAG COAT START

    55.9 ft. - General Observation - 30% MAG COAT START

Observations (23)

DistanceCodeObservation
38SAMSEVERE AGG
90.6TFCCapped
55.9MGO30% MAG COAT START
67TFOpen
120.9TFCCapped
209SSSPEELING FLAKING CONCRETE SEVERE AGG ATTACHED
16.6SSSPEELING FLAKING CONCRETE SEVERE AGG ATTACHED
209.6AMH1:20AM
0MWM
209MGOMAG COAT 30% FINISH
0MGOConn. @ Mh, 3 O' Clock. Active
2SSSFALKING CONCRETE
209SAMSEVERE
0AMH12:50AM
0MWL
16.6SSSFLAKING CONCRETE
148.7TFOpen
209MGOConn. @ Mh, 9 O' Clock. Active
0MGOConn. @ Mh, 9 O' Clock. Active
31.5SSSPEELING CONCRETE SEVERE AGG ATTACHED
87.4TFCCapped
117.9TFOpen
2SAMSEVERE AGG

Properties (6)

custom_field_three
PEELING FLAKING CONCRETE SEVERE AGG ATTACHED
custom_field_two
2
customer
LACSD
datetime
2020-02-26T00:42:24-08:00
documentation
MARTIN,REVELES,CASTILLO
is_lateral_inspection
false