- Date
- 02/12/2020
- W/O
- 808062
- Weather
- Dry
- Operator/Surveyor
- M.MARTINEZ
- Sewer ID
- Z00283
- PipeID
- P04189
- Time
- 2:20 AM
- Certificate
- U-115-06022794
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K7356
- Sewer Name
- 02 MONTEBELLO INTERCEPTOR TRUNK, SECTS 1&2
- City
- MONTEBELLO
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 18
- Purpose
- Routine Assessment
- Project
- RFIR_WO_808062_TV02214_JAN2020
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 30 in.
- Width
- 30 in.
- Upstream MH
- 02 1844
- Downstream MH
- 02 1843
- Dir. of Survey
- Downstream
- Length Surveyed
- 93.1 ft.
- Total Length
- 93.1 ft.
- Structural Index
- 4
- Structural Quick
- 5121
- Structural Rating
- 7
- O&M Index
- 4
- O&M Quick
- 4100
- O&M Rating
- 4
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 11
Pipe schematic from manhole 02 1844 to 02 1843 Observation photos (2)

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start