- Date
- 02/11/2020
- W/O
- 808063
- Weather
- Dry
- Operator/Surveyor
- M.MARTINEZ
- Sewer ID
- Z00284
- PipeID
- P04414
- Time
- 3:41 AM
- Certificate
- U-115-06022794
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K7354
- Sewer Name
- 02 MONTEBELLO INTERCEPTOR TRUNK, SECTION 3
- City
- MONTEBELLO
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 14
- Purpose
- Routine Assessment
- Project
- RFIR_WO_808063_TV02413_JAN2020
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 21 in.
- Width
- 21 in.
- Upstream MH
- 02 2139
- Downstream MH
- 02 1212
- Dir. of Survey
- Upstream
- Length Surveyed
- 185.1 ft.
- Total Length
- 185.1 ft.
- Structural Index
- 3
- Structural Quick
- 3121
- Structural Rating
- 5
- O&M Index
- 3
- O&M Quick
- 4121
- O&M Rating
- 6
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 11
Pipe schematic from manhole 02 2139 to 02 1212 Observation photos (3)

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

112.2 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start