Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 10, 2020, 11:10 AM
  • 02 0898_02 0897_02102020_032053.mp4

Date
02/10/2020
W/O
808148
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00252
PipeID
P03466
Time
3:10 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7253
Sewer Name
02 DOWNEY-BELLFLOWER DIVERSION TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_808148_TV02380_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
02 0898
Downstream MH
02 0897
Dir. of Survey
Downstream
Length Surveyed
352.9 ft.
Total Length
352.9 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
207
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
207
Pipe schematic from manhole 02 0898 to 02 0897
MH: 02 0898MH: 02 0897downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 08986.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start352 ft. MGO - General Observation - Grease Deposits, from 4 to 8 oclock, 5%, throughout the reach352 ft. MGO - General Observation - Surface Spalling from 9 to 3 oclock, throughout the reach352.9 ft. AMH - Downstream Manhole, Survey Ends - 02 0897352.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
352.9AMH02 0897
352MGOGrease Deposits, from 4 to 8 oclock, 5%, throughout the reach
352MGOSurface Spalling from 9 to 3 oclock, throughout the reach
0MWM
0MWL
6.1CM
0AMH02 0898
352.9CM

Properties (6)

additional_info
SC398853
custom_field_two
3
customer
LACSD
datetime
2020-02-10T03:10:33-08:00
documentation
PROPIPE
is_lateral_inspection
false