Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 5, 2020, 06:41 AM
  • 02 0936_02 0935_02042020_225330.mp4

Date
02/04/2020
W/O
808148
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00252
PipeID
P03505
Time
10:41 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7251
Sewer Name
02 DOWNEY-BELLFLOWER DIVERSION TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_808148_TV02380_JAN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
02 0936
Downstream MH
02 0935
Dir. of Survey
Downstream
Length Surveyed
362.9 ft.
Total Length
362.9 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 02 0936 to 02 0935
MH: 02 0936MH: 02 0935downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 093611 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start49.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES362.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish362.9 ft. AMH - Downstream Manhole, Survey Ends - 02 0935

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    49.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
49.1FL
362.9CM
0MWM
362.9AMH02 0935
0MWL
11CM
0AMH02 0936

Properties (6)

additional_info
SC398851
custom_field_two
3
customer
LACSD
datetime
2020-02-04T22:41:51-08:00
documentation
PROPIPE
is_lateral_inspection
false